112.5 kva transformer

The 112.5 kVA transformer is a medium-capacity power transformer, mainly used for converting voltage levels and transmitting

 electrical energy in the power distribution system. The following explanations are carried out from aspects such as **technical 

parameters, calculation methods, application scenarios, and model selection suggestions**:

 I. Core Parameters and Definitions

- **Apparent Power**: 112.5 kVA (kilovolt-ampere), which represents the **total capacity** of the transformer, including active 

power (kW) and reactive power (kVar).

- **Formula Relationships**:

  **Active Power (kW) = 112.5 kVA × Power Factor (cosφ)**

  **Reactive Power (kVar) = 112.5 kVA × Reactive Factor (sinφ)**

 II. Calculation of Rated Current (Single-phase vs. Three-phase)

 1. Single-phase Transformer

- **Rated Voltage**: Commonly 230V/115V (low voltage side) or 10kV/230V (high voltage side).

- **Current Formula**:

  **I (A) = 112,500 VA ÷ Voltage (V)**

  - **Example**: For a 230V single-phase transformer

    **I = 112,500 ÷ 230 ≈ 489A** (current on the low voltage side).

 2. Three-phase Transformer

- **Rated Voltage**: Commonly 400V/230V (low voltage side) or 10kV/400V (high voltage side).

- **Current Formula**:

  **I (A) = 112,500 VA ÷ (√3 × Line Voltage)**

  - **Example**: For a 400V three-phase transformer

    **I = 112,500 ÷ (1.732 × 400) ≈ 162A** (line current on the low voltage side).

# III. Typical Application Scenarios

Field FieldApplication ScenarioLoad Example
Commercial BuildingsPower distribution for shopping malls and office buildingsLighting, air conditioning, elevators (total power < 90kW)
Industrial EquipmentPower supply for small factories and production linesMotors, welding machines (power factor compensation needs to be considered)
Distributed EnergyGrid connection of photovoltaic/wind power, energy storage systemsNew energy power generation systems below 100kW
Special PurposesDedicated for welding machines, power supplies for test equipmentLow voltage and high current scenarios (such as 20V/5,625A)

 IV. Key Technical Parameters




ParameterCommon ValueExplanation
Rated Capacity112.5 kVAStandard specification (can be customized)
Voltage Ratio10kV/400V, 20kV/480V, etc.Needs to match the grid voltage level
Impedance Voltage (Uk%)4% - 6% (three-phase)Affects the short-circuit current and voltage stability
Efficiency98% - 99% (full load)No-load loss < 200W, load loss < 1.5kW
Cooling MethodOil cooling (ONAN), air cooling (OFAF)Oil cooling is suitable for indoor use, and air cooling is suitable for outdoor use
Connection GroupDyn11 (three-phase), Single-phaseDyn11 allows unbalanced three-phase loads

 V. Model Selection and Configuration Suggestions

 1. Load Calculation

- **Active Power Demand**:

  If the total load power is 90kW (cosφ = 0.8), then a transformer of 90kW ÷ 0.8 = 112.5 kVA is required.

- **Impact Load**:

  When welding machines and motors start, the current can reach 5-7 times the rated current. A transformer with an

 overload capacity of 1.2-1.5 times is required.

 2. Voltage Level Matching

- **High Voltage Side**: Select 10kV, 20kV or 35kV according to the power grid.

- **Low Voltage Side**:

  - If the load is mainly single-phase: Select 230V single-phase or 400V/230V three-phase (three-phase four-wire system).

  - If the load is mainly three-phase motors: Select 400V three-phase.

 3. Brands and Standards

- **International Brands**: ABB (SCB14 series), Schneider (SM6 series).

- **Domestic Brands**: TBEA (S13-M series), CHINT (NB series).

- **Standards**: Comply with IEC 60076 (international) or GB 1094 (China).

 VI. Precautions

1. **Power Factor Compensation**:

  If the load power factor < 0.8, parallel capacitors need to be used for compensation, otherwise the actual load-carrying 

capacity of the transformer will decrease.

  **Example**: When cosφ = 0.6, a 112.5 kVA transformer can only carry 67.5 kW of active load.

2. **Short-circuit Protection**:

  The circuit breaker on the high voltage side needs to be selected according to the **short-circuit current** (for example,

 the short-circuit current on the 10kV side can reach 15kA).

3. **Installation Environment**:

  Oil-cooled transformers need to be equipped with an **oil storage tank**, and air-cooled transformers need to ensure

 good ventilation (ambient temperature < 40℃).

**Conclusion**: The 112.5 kVA transformer is suitable for small and medium-sized power distribution scenarios. When

 selecting the model, key attention should be paid to **voltage levels, load types, and power factors**, and a 20% overload 

margin should be reserved to deal with impact loads. In practical applications, it is recommended that professional electrical 

engineers design the scheme according to on-site requirements.