electrical pull box

The detailed analysis of **Electrical Pull Box (Electrical Pulling Box/Pulling Box)** is as follows:

I. Definition and Core Functions

The **Pulling Box** is a kind of box used in the **cable wiring system**, and its main functions are:

1. **Assisting Cable Laying**: When wiring over long distances or along complex paths, it provides a temporary operating space 

to facilitate pulling the cable (reducing friction and damage).

2. **Transition Connection**: It serves as a transition point for the cable from one conduit to another.

3. **Inspection and Maintenance Entrance**: It allows for the inspection and replacement of cables at a later stage without the

 need to damage the wall or floor.

 II. Differences from Junction Box

Type TypeAllowable Cable JointsMain PurposesSizeInstallation Location
Pulling BoxNot AllowedCable pulling, turning, and threadingLarger (depth ≥ 15cm)Straight section ≥ 30 meters or at bends
Junction BoxAllowedCable termination and branchingSmallerNear fixed equipment

III. Main Types and Application Scenarios

1. Classification by Installation Method

Type TypeFeaturesApplicable Scenarios
Surface-mounted Pulling BoxSurface-mounted, with an openable cover for easy inspectionIndustrial plants, below the ceiling



2. Classification by Shape

- **Straight Type (Through Type)**: Used for threading cables in straight sections to reduce resistance.

- **Elbow Type (90°/45°)**: Changes the direction of the cable to avoid right-angle bends (the bending radius ≥ 6 times the outer diameter of the cable).

- **Three-way/Four-way Type**: Connects multiple conduits to form branch paths.

 IV. Core Components and Materials

1. **Box Material**

   - **Metal (Cold-rolled Steel/Stainless Steel)**: High strength, requires grounding, and is suitable for industrial environments.

   - **Plastic (PVC/ABS)**: Corrosion-resistant and has good insulation properties, suitable for indoor or underground scenarios.

2. **Key Components**

   - **Knockout**: A pre-opened hole design that is suitable for different sizes of conduits.

   - **Grounding Terminal**: The metal box must be connected to the ground wire (PE).

   - **Sealing Rubber Ring**: The underground type needs to be equipped with a waterproof rubber ring to prevent water vapor from entering.

 V. Installation Specifications and Key Points

1. NEC (USA) and Chinese Standards

- **NEC 314.28**:

  - A pulling box should be installed every **30 meters** in a straight section;

  - The number of elbows ≤ **2** per 30 meters, otherwise the spacing needs to be shortened.

- **Chinese GB 50169-2016**:

  - When the length of the cable passing through the pipe exceeds **30 meters without bends** or **20 meters with 1 bend**, a pulling box should be installed.