blow transformer
Detailed Explanation and Countermeasures of Transformer Explosion (Blow Transformer)
Combined with American standards and practical application scenarios:
I. Definition and Types
"Blow Transformer" refers to the phenomenon where due to faults in the transformer, internal arcs, overheating, or a sudden
increase in pressure occur, leading to the rupture of the outer shell, sparks, smoke, and even explosions. Common types include:
- **Residential Distribution Transformer** (such as a 480V/240V single-phase transformer)
- **Industrial Transformer** (such as a 2.4kV-34.5kV three-phase transformer)
- **Power Transformer** (used for power grid transmission)
II. Common Causes (with American Standard Basis Attached)
1. Overload
- **Reasons**:
- The load exceeds the rated capacity (for example, when residential air conditioners and electric vehicle charging piles operate
simultaneously).
- **NEC 450.3**: The load of the transformer shall not exceed 100% of the rated power (short-term overload needs to comply with
the temperature rise standard).
- **Consequences**: Overheating of the winding → Decomposition of the insulating oil → Increase in internal pressure.
2. Short Circuit Fault
- **Reasons**:
- Aging of the winding insulation, invasion of small animals, and wear of the cables (About 15% of transformer failures in the
United States are caused by squirrels every year).
- **IEEE C57.12.00**: The transformer needs to be able to withstand a short-circuit impact of 3-10 times the rated current.
- **Consequences**: The instant large current causes the winding to deform and arc discharge.
3. Insulation Failure
- **Reasons**:
- Contamination of the insulating oil (moisture, impurities), and aging due to high temperature (the insulation grade is lower
than the ambient temperature).
- **UL 1561**: The insulating oil of the transformer needs to pass the dielectric strength test (≥30kV).
- **Case**: During the wildfires in California in 2024, 3 transformers caught fire due to insulating oil leakage.
4. Lightning Strike and Overvoltage (Surge)
- **Data**: About 22% of transformer failures in the United States are caused by lightning every year (as statistically analyzed by IEEE).
- **Protection**:
- **NEC 285**: A surge protector (SPD) needs to be installed, and the discharge current ≥10kA.
- **IEEE C62.11**: The distance between the lightning arrester and the transformer needs to be <15 meters.
5. Manufacturing Defects
- **Typical Problems**: Poor winding welding, design defects of the radiator (such as GE recalling 1000 transformers in 2023).
III. Fault Signs and Emergency Handling
1. Early Warning Signals
Phenomenon | Possible Reason | Risk Level |
Abnormal noise ("buzzing" sound becomes sharper) | Loose iron core or overload | Medium |
The box body is hot or leaking oil | Decomposition of the insulating oil or failure of the seal | High |
Smoking or sparking | Internal arc | Extremely high |
2. Emergency Steps (Standards of American FirstEnergy Corporation)
1. **Power Off**: Immediately disconnect the high and low voltage side circuit breakers of the transformer (preferably use remote control).
2. **Isolate the Site**: Set a safe distance (for high-voltage transformers, it needs to be ≥10 meters), and hang a "Danger" sign.
3. **Extinguish the Fire**: Use a dry powder fire extinguisher (Class ABC), and do not use water (when the insulating oil is burning).
4. **Report**: Notify the power company (such as Florida Power & Light) and the fire department (refer to the NFPA 70E standard).
IV. Preventive Measures (Classified by Scenarios)
1. Residential Distribution Transformer
- **Model Selection**:
- Capacity: Calculate according to the residential load (1.2-1.5 times the peak power, for example, a 50kVA transformer supplies 20 households).
- Brands: Cooper Power Systems and Eaton are recommended.
- **Installation**:
- **NEC 110.26**: The distance between the transformer and the building needs to be ≥3 meters (to prevent the spread of fire).
- Grounding: Adopt **Ufer grounding** (steel bars in the concrete + grounding rod), and the resistance <5Ω.
2. Industrial Transformer
- **Monitoring System**:
- Install an **online oil chromatograph analyzer** (such as GE D60) to detect fault gases such as H₂ and CH₄ in real time.
- Temperature sensor: Set the threshold at 105°C (trigger an alarm if exceeded, IEEE C57.91 standard).
- **Maintenance**:
- Replace the insulating oil every 2 years (ASTM D3487 standard), and check the DC resistance of the winding.
3. Outdoor Transformer
- **Protection Level**:
- **NEMA 3R** (rainproof) or **NEMA 4X** (anti-corrosion), and install a bird protection net (aperture <5cm).
- **Environment**:
- There should be no weeds or combustibles around (in line with the NFPA 70B "Electrical Equipment Maintenance Standard").
V. Relevant Standards and Regulations
Standard | Content |
NEC Article 450 | Transformer installation and protection |
IEEE C57.109 | Calculation of short-circuit current for distribution transformers |
OSHA 1910.302 | Safety operation specifications for industrial transformers |
NFPA 85 | Fire protection standard for rotating electrical equipment (including transformers) |
VI. Analysis of Fault Cases
**The Transformer Explosion Incident in a Miami Apartment in 2024**
- **Reasons**:
- Severe unbalance of the three-phase load (single-phase load accounts for 85%) leads to the drift of the neutral point.
- Failure to regularly detect the load balance as required by **NEC 210.10**.
- **Lessons**:
- Install an **automatic load balancing device** (such as ABB PCS 100).
- Mandatorily replace old transformers (>20 years old).
**Conclusion**: The explosion of transformers needs to be prevented through **appropriate model selection, regular maintenance,
and overvoltage protection**. When a fault occurs, follow the NEC and NFPA standards to cut off the power and isolate the site.
In the American market, brands such as **Cooper Power** and **Eaton** that have passed the UL certification are recommended.
Pay attention to the compliance of grounding and the environment during installation.