Detailed Explanation of Power Breaker Switch

I. Core Functions and Types

1. **Basic Functions**

   - **Overload Protection**: Automatically disconnects when the current exceeds the rated value.

   - **Short Circuit Protection**: Quickly cuts off the circuit when there is a large instantaneous current (the response time is usually ≤ 0.1 seconds).

   - **Under-Voltage/Over-Voltage Protection** (for some high-end models): Trips when the voltage is abnormal.

2. **Common Types**

   - **Miniature Circuit Breaker (MCB)**:

     - Current range: 1A - 125A, used for residential or small commercial power distribution.

     - Breaking capacity: 6kA - 15kA (commonly 6kA/10kA for household use).

   - **Molded Case Circuit Breaker (MCCB)**:

     - Current range: 100A - 1600A, suitable for industrial or large building applications.

     - Breaking capacity: 15kA - 150kA (industrial grade can reach over 100kA).

   - **Residual Current Device (RCD)**:

     - With an additional leakage protection function, the operating current is 30mA (for household use) or above 100mA (for industrial use).

II. Key Parameters for Model Selection

1. **Rated Current (In)**

   - Calculation formula:

  1743228505381.png

   - **Example**: For a household with a total power of 10kW (220V, power factor of 0.8), the calculated current is approximately 56.8A, and a 63A circuit breaker can be selected.

2. **Breaking Capacity (Icu/Ics)**

   - **Icu**: Ultimate breaking capacity (the maximum one-time short-circuit current).

   - **Ics**: Service breaking capacity (the current that can be broken repeatedly).

   - **Selection principle**: Icu ≥ Expected short-circuit current at the installation point (data can be obtained from the power supply company).

3. **Number of Poles (Pole)**

   - **1P**: Single pole (only disconnects the live wire, used for lighting circuits).

   - **2P**: Double pole (disconnects the live wire + neutral wire, used for sockets or the main switch).

   - **3P/4P**: Three-phase circuit breakers (for industrial equipment or three-phase power supply systems).

III. Comparison between Residential and Industrial Applications

Parameter Items Residential Scenario (MCB)Industrial Scenario (MCCB)
Typical Current 16A - 63A100A - 1600A
Breaking Capacity6kA - 10kA15kA - 150kA
Protection FunctionsOverload + Short Circuit + Leakage (RCD optional)Overload + Short Circuit + Ground Fault + Under-Voltage
Installation MethodRail-mounted (35mm standard)Drawer type or fixed type
Accessory ExpansionOptional auxiliary contacts, alarm modulesSupports electric operation, communication modules (Modbus)

IV. Key Points of Installation and Maintenance

1. **Installation Steps**

   - **Power-off Operation**: First disconnect the upper-level power supply and carry out construction after verifying that there is no electricity.

   - **Wiring Specifications**:

     - Connect the live wire to the upper terminal of the circuit breaker, and connect the neutral wire to the neutral busbar (do not connect it to the circuit breaker).

     - The ground wire needs to be directly connected to the grounding terminal of the box.

   - **Fixing Requirements**: Use screws to fasten tightly to avoid excessive contact resistance caused by looseness.

YouTube:https://youtube.com/shorts/dzB4hVFjRnI 

2. **Troubleshooting of Common Problems**

   - **Frequent Tripping**:

     - Reasons: Excessive load, line short circuit, leakage, aging of the circuit breaker.

     - Solutions: Check the load distribution and measure the insulation resistance with a multimeter (≥ 0.5MΩ).

   - **Contact Ablation**:

     - Phenomenon: Blackened contacts and poor contact.

     - Treatment: Polish with fine sandpaper or replace the circuit breaker.

3. **Maintenance Cycle**

   - Residential: Check the wiring terminals once every 2 to 3 years.

   - Industrial: Conduct a comprehensive overhaul every year, and test the breaking time and operating characteristics.

V. Brand Recommendations

1. **High-end for Household Use**:

   - Schneider C65 series, ABB T2/T3 series.

2. **Economical for Household Use**:

   - CHNT DZ47 series, DELIXI CDB6 series.

3. **Industrial Grade**:

   - Siemens 3VL series, Eaton 9E series.

VI. Precautions

1. **Coordination between Upper and Lower Levels**

   - The breaking capacity of the upper-level circuit breaker needs to be greater than that of the lower-level one to avoid越级跳闸 (越级 tripping).

2. **Environmental Requirements**

   - Installation environment temperature: -5°C to +40°C (derating is required if exceeded).

   - Humidity: ≤ 90%RH (without condensation).

3. **Compliance Standards**

   - Comply with GB 10963 (for household use) or GB 14048.2 (for industrial use).